| Ventilation
Requirements
Air
change ratings
The
simplest method of determining the ventilation rate required
is to make use of the accumulated experience of the industry
expressed in a table of air change rates. The volume in
cubic metres (m3) of the space to be ventilated is calculated
and multiplied by the number of air changes per hour to
give the ventilation rate in m3 per hour. Division by 3.6
converts this to litres per second.
Ventilation
rate (litre/s) = Volume (m³) x air changes per hour / 3.6
The
table below gives a guide to the number of air changes generally
recommended. Provided air inlets and outlets are properly
sited, the tabulated values will be sufficient for air movement
requirements. They will also meet requirements for pollution
and moisture removal, in typical examples of the accommodation
indicated, and heat removal requirements in temperate climates
without heat sources.
However,
particular installations should always be checked against
the following questions:
-
Are there specific bylaws or other legal requirements
applicable in the locality?
- Is
the space expected to become so crowded that a higher
ventilation rate might be obtained by calculating on a
per person basis?
- Are
there abnormal sources of heat or fumes?
-
Is it desirable to provide a higher ventilation rate for
summer cooling?
Ventilation
rates per person
Each
human being produces their personal quota of heat, water
vapour, carbon dioxide and body odour. The ventilation requirement
for the last item will cover the needs of the other three
during the heating season. It is not sufficient merely to
ensure an acceptable average freshness of atmosphere throughout
the room; if people are crowded together by shortage of
space the average odour concentration must be reduced. This
means that the fresh air supply per person must increase
with the number of people in a room, and consequently the
air change rate must increase. Recommended minimum fresh
air supply.
Recommended
minimum fresh air supply
3m3
|
17
litre/s |
20 |
| 6 |
11 |
6.5 |
| 9 |
8 |
3.2 |
| 12 |
6 |
1.8 |
These
rates should be increased by a third if smoking is permitted
or if there are doubts about standards of personal hygiene.
If minimum legal requirements are specified, they are generally
about a third less. In contrast, as little as 1 litre/s
will suffice to meet the strictly physiological needs of
one person for oxygen supply and carbon dioxide limitation.
Further
calculations on air changes per hour will come later.
Consideration
of dust and odours in a normal office or workroom ventilation
job can usually be ignored when preparing the scheme, as
the rate of ventilation needed to give comfortable conditions
based on temperature, humidity and air movement - 6 to 10
ACH - would be considerably higher than that required to
keep dust and odours down to a comfortable level - about
1 to 2 ACH.
Incidentally,
it is always advisable when dealing with a fairly crowded
space (e.g. auditoria, dance halls) to give a quick check
for the minimum air volume required by allowing 28m3/h per
person. This is to prevent body odours from becoming a nuisance.
Also the carbon dioxide content of the air, gradually increasing
due to the CO2 exhaled from the lungs, should be prevented
from exceeding 10 parts per 10,000. This calculation is
commonly used as the maximum CO2 concentration desirable
in a closed occupied space.
Before
you begin to think that this is getting rather complicated,
be reassured that in practice if we design a normal ventilation
scheme to deal with temperature rise and air movement, the
remaining factors of humidity and purity (concentration
of CO2, odours and dust) are taken care of. There are exceptions
to this in the case of humidity and dust, but they usually
occur in the more specialised applications where the requirements
are either for full air conditioning with dehumidification
by refrigeration for humidity control, or for specific dust
removal.
|